3 Cores Power Cable (XLPE Insulated)
Characteristics
Rated Temperature |
90℃-100℃ |
Rated Voltage |
600/1000V |
Reference Standard |
IEC60502 |
Conductors |
Stranded copper conductors, both shaped and circular |
Insulation |
Cross-linked polyethylene (XLPE) compound |
PVC bedding |
|
Flame-retardant PVC sheathing overall |
Applications
Intended for fixed installations in transmission and distribution systems, tunnels, pipelines, and similar applications.
Not intended for situations requiring resistance to external mechanical forces.
Specifications
Cross-sectional Area (mm²) |
No.&diameter of wire (N/mm) |
Average overall diameter (mm) |
Reference weight (kg/km) |
Conductor Resistance (Ω/km) |
3x1.5 |
1/1.38 |
12.5 |
202 |
12.1 |
3x2.5 |
1/1.76 |
13.3 |
245 |
7.41 |
3x4.0 |
7/0.85 |
15 |
332 |
4.61 |
3x6.0 |
7/1.04 |
16.1 |
414 |
3.08 |
3x10 |
7/1.35 |
18.3 |
586 |
1.83 |
3x16 |
7/1.7 |
20.4 |
810 |
1.15 |
3x25 |
10/1.83 |
19.6 |
943 |
0.727 |
3x35 |
14/1.83 |
21.4 |
1245 |
0.524 |
3x50 |
19/1.83 |
23.6 |
1656 |
0.387 |
3x70 |
27/1.83 |
27.8 |
2282 |
0.268 |
3x95 |
37/1.83 |
30.3 |
3032 |
0.193 |
3x120 |
30/2.32 |
33.9 |
3845 |
0.153 |
3x150 |
37/2.32 |
37.2 |
4681 |
0.124 |
3x185 |
37/2.52 |
40.7 |
5706 |
0.0991 |
3x240 |
48/2.52 |
46.4 |
7301 |
0.0754 |
3x300 |
61/2.52 |
51.4 |
9161 |
0.0601 |
3x400 |
61/2.95 |
58.6 |
12398 |
0.047 |