AAC All Aluminum Conductor DIN 48201 Standard
Applications
All Aluminium Conductor (AAC) widely used in power transmission lines with various voltage levels, principally used in urban areas where spacing is short and the supports are close. They can be used in coastal regions owing to its high degree of corrosion resistance and extensively within the Railway and Metro industries.
Construction
Concentric lay stranded Aluminium Conductor (AAC) is made up of one or more strands of hard drawn 1350 aluminum wires, concentrically stranded.
Feature
| Electrical Properties | |
| Density at 20°C | 2.703 kg/dm |
| Temperature Coefficient at 20°C | 0.00403 (°C) |
| Resistivity at 20°C | 0.028264 |
| Linear Expansivity | 23 x10-6(°C) |
Standard
ASTM B 231, BS EN-50182, CSA C 61089, AS/NZS 1531,DIN 48201,IEC 61089,GB/T 1179, JIS 3109 etc
Packing material
Wooden drum, steel-wooden drum, steel drum.
Specification
DIN 48201 Part 5 Specification for Aluminium stranded conductors.
Specifications
AAC All Aluminum Conductor DIN 48201 Part 5 Standard Parameters
| Nominal Area | Stranding | Overall Diameter | Weight | Rated Strength | Electrical Resistance | Current Rating | |
| Nominal | Teorical | ||||||
| mm² | mm² | No./mm | mm | kg/km | KN | Ω/KM | A |
| 16 | 15.89 | 7/1.70 | 5.1 | 43 | 2.84 | 1.8022 | 83 |
| 25 | 24.25 | 7/2.10 | 6.3 | 66 | 4.17 | 1.181 | 108 |
| 35 | 34.36 | 7/2.50 | 7.5 | 94 | 5.78 | 0.8333 | 134 |
| 50 | 49.48 | 7/3.00 | 9 | 135 | 7.94 | 0.5787 | 168 |
| 50 | 48.35 | 19/1.80 | 9 | 133 | 8.45 | 0.5951 | 166 |
| 70 | 65.81 | 19/2.10 | 10.5 | 181 | 11.32 | 0.4372 | 200 |
| 95 | 93.27 | 19/2.50 | 12.5 | 256 | 15.68 | 0.3085 | 248 |
| 120 | 116.99 | 19/2.80 | 14 | 322 | 18.78 | 0.2459 | 285 |
| 150 | 147.11 | 37/2.25 | 15.8 | 406 | 25.3 | 0.196 | 328 |
| 185 | 181.62 | 37/2.50 | 17.5 | 500 | 30.54 | 0.1588 | 373 |
| 240 | 242.54 | 61/2.25 | 20.3 | 670 | 39.51 | 0.1191 | 445 |
| 300 | 299.43 | 61/2.50 | 22.5 | 827 | 47.7 | 0.0965 | 506 |
| 400 | 400.14 | 61/2.89 | 26 | 1104 | 60.86 | 0.0722 | 602 |
| 500 | 499.83 | 61/3.23 | 29.1 | 1379 | 74.67 | 0.0578 | 688 |
| 625* | 626.2 | 91/2.96 | 32.6 | 1732 | 95.25 | 0.0462 | 786 |
| 800* | 802.09 | 91/3.35 | 36.9 | 2218 | 118.39 | 0.036 | 907 |
| 1000* | 999.71 | 91/3.74 | 41.1 | 2767 | 145.76 | 0.0289 | 1026 |
The items marked with “*” are not in our current product range and the details are for information only.
Note: The values of current rating mentioned in above Table are based on wind velocity of 0.6 metre/second, solar heat radiation of 1200 watt/metre2, ambient temperature of 50° C & conductor temperature of 80°C.