Leave Your Message
Products Categories
Featured Products

AS/NZS standard 19/33kV XLPE Insulated MV Medium Voltage Power Cable

Power distribution or secondary transmission network cables are commonly used as the main power source for commercial, industrial, and urban residential networks. Suitable for high fault level systems with rated currents up to 10kA/second. Structures with higher fault current ratings can be provided upon request.

Medium voltage(MV) cable:
The cross-sectional size range of 10kV, 11kV, 20kV, 22kV, 30kV, and 33kV cables is as follows (depending on copper/aluminum conductors): 35mm2 to 1000mm2.

Larger sizes can be provided upon request.

    Application

    Power distribution or secondary transmission network cables are commonly used as the main power source for commercial, industrial, and urban residential networks. Suitable for high fault level systems with rated currents up to 10kA/second. Structures with higher fault current ratings can be provided upon request.

    Temperature range

    Install min temperature

    0°C

    Working max temperature

    +90°C

    Working min temperature

    -25 °C

    Min bending radius

    Install cables

    12D (PVC)  15D (HDPE)

    During installation

    18D (PVC) 25D (HDPE)

    Resistance to Chemical exposure

    Accidental

    Mechanical impact

    Light (PVC)  Heavy (HDPE)

    Water exposure

    XLPE – Spray  EPR – Immersion/Temporary coverage

    Solar radiation and weather exposure

    can be direct exposure.

    Construction

    Manufacturing and type testing in accordance with AS/NZS 1429.1, IEC: 60502-2 or equivalent

    Structure:  1 core, 3 core, 3×1 core Triplex

    Conductor: Cu or AL, Stranded Circular, twisted Compact Circular, Milliken Segmented

    Insulate: XLPE / TR-XLPE / EPR

    Metallic screen or sheath: Copper Wire Screen (CWS), Copper Tape Screen (CTS), Lead alloy sheath (LAS), Corrugated Aluminium sheath (CAS), Corrugated Copper sheath (CCU), Corrugated Stainless Steel (CSS), Aluminium poly laminated (APL), Copper Poly Laminated (CPL), Aldrey wire screen (AWS)

    Armour – Aluminium Wire Armour (AWA), Steel Wire Armour (SWA), Stainless Steel Wire Armour (SSWA)

    Anti termite: Polyamide Nylon Jacket, Double brass tape (DBT), Cypermethrin

    Black 5V-90 polyvinyl chloride (PVC): standard

    Orange 5V-90 PVC inner layer with black high density

    Polyethylene (HDPE) outer : alternative

    Low smoke zero halogen (LSOH) : alternative

    Data Sheet

    19/33kV-Power cable

    Cores x Nominal Area

    Conductor diameter (Approx.)

    Nominal Insulation Thickness

    Approx. CWS area on each core

    Nominal Thickness of PVC Sheath

    Overall Cable diameter (+/- 3.0)

    Short Circuit rating of Conductor/ CWS

    Cable Weight (Approx.)

    Max. Conductor DC Resistance at 20 °C

    No. X mm2

    mm

    mm

    mm2

    mm

    mm

    kA for 1sec

    kg/km

    (Ω/km)

    1C x 70 9.7 8.0 79 2.1 37.4 10 / 10 2492 0.268
    1C x 95 11.4 8.0 79 2.1 39.3 13.6 / 10 2736 0.193
    1C x 120 12.8 8.0 79 2.2 40.6 17.2 / 10 3034 0.153
    1C x 150 14.2 8.0 79 2.2 42.0 21.5 / 10 3357 0.124
    1C x 185 16.1 8.0 79 2.3 44.1 26.5 / 10 3766 0.0991
    1C x 240 18.5 8.0 79 2.4 46.7 34.3 / 10 4374 0.0754
    1C x 300 20.6 8.0 79 2.4 48.8 42.9 / 10 4992 0.0601
    1C x 400 23.6 8.0 79 2.5 52.2 57.2 / 10 6036 0.047
    1C x 500 26.6 8.0 79 2.6 55.4 71.5 / 10 7072 0.0366
    1C x 630 30.2 8.0 79 2.7 59.2 90.1 / 10 8402 0.0283