Leave Your Message
Products Categories
Featured Products

SANS Standard 3.8/6.6kV XLPE Insulated MV Middle Voltage Power Cable

Copper or Aluminium Conductors, single or three core, armoured or unarmoured, bedded and served in PVC or non-halogenated material, rated voltage from 6,6kV up to 33kV, manufactured according to SANS or other National or International Standards.

    Application

    3.8/6.6kV cables may be more flexible, such as single core coil end lead type 4E designed for motors, generators, actuators, transformers and circuit breakers, with its CPE rubber outer sheath. Notes: this cable has a voltage range of 300/500V to 11kV.

    Construction

    Conductor: Class 2 stranded copper conductorConductor Screen: Semi-conductive XLPE (Cross-Linked Polyethylene)Insulation: XLPE (Cross-Linked Polyethylene)Insulation ScreenSemi-conductive XLPE (Cross-Linked Polyethylene)Metallic ScreenIndividual or collective overall copper tape screenBedding PVC (Polyvinyl Chloride)ArmourSingle core: AWA (Aluminium Wire Armoured)Multi-core: SWA (Steel Wire Armoured)Sheath:PVC (Polyvinyl Chloride)Sheath: Colour Red Black

    Cable Identification

    MFRPVC (red stripe), LHFRPVC (blue stripe), HFFR (white stripe), PE (no stripe).

    Characteristics

    Rated voltage: 3800/6600V –SANS1339

    Temperature limits: -15°C to +90°C

    Should not be installed at temperatures below 0°C or above +60°C

    Data Sheet

    3.8/6.6kV 1CORE AL/XLPE/PVC/AWA/PVC AND CU/XLPE/PVC/AWA/PVC Type A

    Conductor size

    mm²

    50

    70

    95

    120

    150

    185

    240

    300

    400

    500

    630

    Conductor diameter

    mm

    8.50

    10.00

    12.00

    13.50

    15.00

    16.50

    19.00

    21.50

    24.00

    27.50

    31.50

    Insulation diameter

    mm

    15.00

    17.00

    18.50

    20.00

    21.50

    23.00

    26.00

    28.50

    33.50

    37.50

    41.50

    Bedding diameter

    mm

    20.00

    21.50

    23.50

    24.50

    26.00

    28.00

    30.50

    33.50

    38.00

    42.50

    46.50

    Armour diameter

    mm

    23.00

    24.50

    26.50

    28.00

    29.50

    32.00

    34.50

    37.50

    42.00

    47.50

    51.50

    Cable diameter

    mm

    27.00

    29.00

    31.00

    32.00

    34.00

    37.00

    40.00

    42.00

    47.00

    53.00

    58.00

    Cable mass (approximate)

    kg/m

    1.263

    1.496

    1.824

    2.098

    2.449

    2.941

    3.537

    4.317

    5.433

    6.729

    8.148

    DC Resistance at 20°C

    Ω/km

    0.387

    0.268

    0.193

    0.153

    0.124

    0.099

    0.075

    0.060

    0.047

    0.037

    0.028

    AC Resistance at 90°C

    Ω/km

    0.494

    0.342

    0.247

    0.196

    0.160

    0.128

    0.099

    0.080

    0.064

    0.052

    0.042

    3.8/6.6kV 1CORE AL/XLPE/UNARMORED/PVC AND CU/XLPE/UNARMORED/PVC Type B

    Conductor size

    mm²

    50

    70

    95

    120

    150

    185

    240

    300

    400

    500

    630

    Conductor diameter

    mm

    8.50

    10.00

    12.00

    13.50

    15.00

    16.50

    19.00

    21.50

    24.00

    27.50

    31.50

    Insulation diameter

    mm

    15.00

    17.00

    18.50

    20.00

    21.50

    23.00

    26.00

    28.50

    33.50

    37.50

    41.50

    Cable diameter

    mm

    21.00

    23.00

    25.00

    27.00

    28.00

    30.00

    33.00

    36.00

    41.00

    45.00

    49.00

    Cable mass (approximate) kg/m

    0.941

    1.192

    1.41

    1.739

    1.931

    2.308

    2.949

    3.524

    4.647

    5.646

    7.031

    DC Resistance at 20°C

    Ω/km

    0.387

    0.268

    0.193

    0.153

    0.124

    0.099

    0.075

    0.060

    0.047

    0.037

    0.028

    AC Resistance at 90°C

    Ω/km

    0.494

    0.342

    0.247

    0.196

    0.160

    0.128

    0.099

    0.080

    0.064

    0.052

    0.042

    3.8/6.6kV 3CORE AL/XLPE/PVC/SWA/PVC AND CU/XLPE/PVC/SWA/PVC Type A

    Conductor size

    mm²

    16

    25

    35

    50

    70

    95

    120

    150

    185

    240

    300

    Conductor diameter

    mm

    4.8

    6.0

    7.2

    8.4

    9.9

    11.7

    13.4

    14.6

    16.4

    18.8

    20.4

    Insulation diameter

    mm

    11.6

    12.8

    14.0

    15.2

    16.7

    18.5

    20.2

    21.4

    23.2

    25.8

    27.8

    Bedding diameter

    mm

    32.6

    35.2

    37.8

    40.6

    43.8

    47.9

    51.8

    54.4

    58.5

    64.3

    68.8

    Armour diameter

    mm

    36.6

    39.2

    41.8

    45.6

    48.8

    52.9

    56.8

    59.4

    64.8

    70.6

    75.1

    Cable diameter

    mm

    41.1

    43.7

    46.5

    50.7

    54.1

    58.4

    62.5

    65.3

    70.9

    77.2

    82.3

    Cable mass (approximate) kg/m

    3.041

    3.536

    4.007

    5.103

    6.049

    7.272

    8.229

    9.319

    11.54

    13.86

    16.37

    DC Resistance at 20°C

    Ω/km

    1.150

    0.727

    0.524

    0.387

    0.268

    0.193

    0.153

    0.124

    0.099

    0.075

    0.060

    AC Resistance at 90°C

    Ω/km

    1.466

    0.927

    0.668

    0.494

    0.342

    0.247

    0.196

    0.160

    0.128

    0.099

    0.080

    3.8/6.6kV 3CORE AL/XLPE/UNARMORED/PVC AND CU/XLPE/UNARMORED/PVC Type B

    Conductor size

    mm²

    16 25

    35

    50

    70

    95

    120

    150

    185

    240

    300

    Conductor diameter

    mm

    4.8

    6.0

    7.2

    8.4

    9.9

    11.7

    13.4

    14.6

    16.4

    18.8

    20.4

    Insulation diameter

    mm

    11.6

    12.8

    14.0

    15.2

    16.7

    18.5

    20.2

    21.4

    23.2

    25.8

    27.8

    Bedding diameter

    mm

    30.6

    33.1

    35.7

    38.3

    41.6

    45.0

    48.7

    51.3

    55.2

    60.8

    65.1

    Cable diameter

    mm

    34.7

    37.5

    40.2

    43.0

    46.5

    50.2

    54.0

    56.8

    60.9

    67.0

    71.7

    Cable mass (approximate)

    kg/m

    1.054

    1.860

    2.220

    2.675

    3.400

    4.039

    4.850

    5.901

    6.918

    8.727

    10.74

    DC Resistance at 20°C

    Ω/km

    1.150

    0.727

    0.524

    0.387

    0.268

    0.193

    0.153

    0.124

    0.099

    0.075

    0.060

    AC Resistance at 90°C

    Ω/km

    1.466

    0.927

    0.668

    0.494

    0.342

    0.247

    0.196

    0.160

    0.128

    0.099

    0.080